PIPE-FLO Professional 2009 or earlier only!

Since PIPE-FLO Professional uses the Darcy-Weisbach method to calculate pipeline pressure losses, an iterative method must be employed in some cases when analyzing compressible fluid systems.  This article discusses the restrictions for using the Darcy-Weisbach method on compressible fluid systems and uses a small steam distribution system to demonstrate the iterative analysis procedure.

The Darcy-Weisbach method assumes that the fluid density remains constant throughout the length of a pipe segment, which is a valid assumption for incompressible fluids (liquids) but not always the case for compressible fluids in which the density is a function of the fluid pressure (fluids such as steam, air, and most industrial gases).  However, with some restrictions, the Darcy-Weisbach method can be extended to analyze compressible fluid systems.  Perry's Chemical Engineers' Handbook states that the Mach number (velocity divided by the speed of sound in the fluid) must not exceed 0.1 to 0.2 in order for compressibility effects to be assumed negligible.  The Crane Technical Paper 410 gives the following pressure drop restrictions:

  1. If the calculated pressure drop in a pipeline (Pin - Pout) is less than 10% of the absolute inlet pressure, acceptable accuracy is obtained if the density used for the fluid is based upon either the inlet or outlet conditions.
  2. If the calculated pressure drop (Pin - Pout) is greater than 10% but less than 40% of the absolute inlet pressure, the Darcy-Weisbach method provides acceptable accuracy if the fluid density is based upon the average of the inlet and outlet fluid conditions.
  3. If the calculated pressure drop (Pin - Pout) is greater than 40% of the absolute inlet pressure, the Darcy-Weisbach method will not give valid results.

PIPE-FLO does not automatically account for changes in fluid density due to the calculated pipeline pressure drops.  Once a fluid pressure has been specified by selecting a fluid zone for the pipeline's design, the density corresponding to that pressure is used throughout the analysis, regardless of the pressures calculated at the pipeline endpoints.  If any of the pipeline pressure drops in a compressible fluid system fall within the 10% to 40% range described in item 2, an iterative analysis procedure must be used.  This article will show you a couple different ways to perform this analysis, both manually and by using X-Link.

NOTE:  When checking the magnitude of the pressure drop (i.e. checking to see if the pressure drop is greater than 10% of the pipeline inlet pressure), be sure to compare it to 10% of the inlet pressure in absolute pressure units.  For example, if the pipeline has an inlet pressure of 100 psig, you would first add the atmospheric pressure to this value (100 psig + 14.7 psia), then take 10% of 114.7 psia and compare that to the pipeline pressure drop.

Iterative Analysis Example - manual method

In this article we will be analyzing the example steam distribution system shown below in Figure 1.  You can open the steam distribution system.pipe attachment at the bottom of this article in PIPE-FLO if you would like to work along yourself.


Figure 1:  Steam Distribution System

The system has an inlet pressure of 150 psig and five subsystems to which it must provide the indicated flow rates.  PIPE-FLO will be used to determine the system pressure losses from the main inlet to each subsystem inlet.

The lineup for the example steam distribution system consists of setting the pressure to 150 psig at the system inlet and setting the required subsystem flow demands at nodes A, B, C, D, and, E (the subsystem inlet nodes).  This lineup will be used throughout the analysis.  Since we will be adjusting the fluid pressure in each pipeline as the analysis proceeds, a fluid zone for each pipeline has been created.  As a starting point we will assume constant fluid properties throughout the system, so the fluid properties for each fluid zone in the system are set as Steam at 500°F and 150 psig.

After the initial results are calculated, the nodal pressures are reviewed to determine which pipeline fluid pressures must be adjusted.  If a pipeline pressure drop is < 10% of its inlet absolute pressure, the pipeline fluid zone pressure is set equal to the inlet gage pressure of the pipeline.  If a pipeline pressure drop is between 10% to 40% of the pipeline inlet pressure, the fluid pressure is set equal to the average of the pipeline endpoint pressures.  The table below shows the approximate calculated gage pressures at the nodes after the first calculation. 

 INLET A B C D E
 150 134 128 120 94 91


If you add the atmospheric pressure and calculate the 10% and 40% values, you will come up with the data in the table below:

  INLETABCD
 10% 16.5 14.9 14.3 13.5 10.9 10.6
 40% 65.9 59.5 57.1 53.9 43.5 42.3


Now let's look at the differential pressures in the pipelines.  The table below shows the pipeline dP's.

PIPE 01PIPE 02PIPE 03PIPE 04PIPE 05 
 15.8 6.18.725.43.3 


From this data, you can see that PIPE 04 is the only pipeline which has a dP (25.4 psi) greater than 10% of its absolute inlet pressure (10% @ node C = 13.4 psia).  So the fluid zone pressure for PIPE 04 should be adjusted to the average of the inlet and outlet gage pressures.  (119.4 psig + 94.0 psig)/2 = 106.7 psig.  The rest of the pipeline fluid zone pressures should be set to their respective inlet pressures.  The table below shows what the fluid zone pressures should be for each of the pipelines for the next iteration:

PIPE 01PIPE 02PIPE 03PIPE 04PIPE 05 
150 134128106.794


After the pipeline fluid properties are adjusted the lineup is run again and the pipeline pressures readjusted as necessary.  This process is repeated until the pipeline pressure drops have stabilized, that is, until they do not change by a significant amount from one iteration to the next.  Note that we will also want to watch for any pipelines that have pressure drops > 40% of their inlet pressures, since using the Darcy-Weisbach method in such cases does not give valid results.


Iterative Analysis Example - "X-Link" method

If you have Microsoft Excel, you can use the X-Link function in conjunction with PIPE-FLO to assist you in the iterative process.  First, re-open the PIPE-FLO example without saving any of the changes you made.  Then open the steam distribution system.xls attachment at the bottom of this article in Excel.  This spreadsheet has been set up to load various data from the PIPE-FLO project including the atmospheric pressure, node pressures, pipeline dPs and fluid zone pressures.  It calculates the absolute node pressures and compares them to the pipeline dPs.  Finally, it checks the current fluid zone pressures, and if the calculations require that any of them need to be adjusted, it assigns a new fluid zone pressure.  Note the "J" column indicates that the fluid zones were all set to 150 psig prior to the first iteration.  The "K" column indicates the pressure that the fluid zones need to be adjusted to, and the "L" column performs the assignment.  First, we have to program the assignment codes into the "L" column though.

In cell "L-6" type the following bolded code:  =pfeassign(I6,"fluid.pressure",K6)  Then, after you've entered this code, highlight cell "L-6" and drag it down to "L-10".  This will fill the assignment codes for all the pipelines.

To perform the next iteration, simply click the read/write button  on the Excel toolbar.  Note the changes in the "Current Fluid Zone Pressure" in column J.  Click the read/write button several more times and note the changes.  After about 5 iterations, the fluid zone pressures become stable and no longer change.  You have reached a solution.

Attachments:

steam distribution system.pipe

steam distribution system.xls

 

  • No labels